Special Conditions For Safe Use (Tüv 14 Atex 148929 X) - WAGO 750-632 Manual

Proportional valve module for wago-i/o-system 750
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

142
Use in Hazardous Environments
Pos : 122.16 /Seri e 750 ( WAGO-I/O-SYSTEM)/Einsatz in Ex- Ber eichen/Bes ondere Bedingungen für den sicheren Ex-Betrieb g em. ATEX-Z ertifi kat TÜ V 14 AT EX 148929_X @ 21\mod_1416995371807_21.doc x @ 169118 @ 3 @ 1
12.2.1
Special Conditions for Safe Use (TÜV 14 ATEX 148929 X)
1.
The modules of the WAGO-I/O-SYSTEM 750-*** have to been erected in
such a way, that corresponding to EN 60079-15 a degree of protection of at
least IP 54 according to EN 60529 is achieved.
2.
Measures have to been taken, external to the modules, to provide a transient
protection that ensures that the rated voltage, connected to the power supply
terminals, is not exceeded by more than 40 %.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted if no explosive atmosphere exists. This although applies for
the all switches, interfaces (Fieldbus, Ethernet, Serial) and the SD-card.
4.
The ambient temperature range is: 0 °C ≤ T
The ambient temperature range for modules with suffix extension /025-****
is: -20 °C ≤ T
Pos : 122.17 /D okumentati on allgemein/Gliederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
≤ +60 °C
amb
Version 1.3.0, valid from FW/HW-Version 01/01
WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
≤ +60 °C
amb
Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-632/000-100

Table of Contents