Table 45: Status Byte S0; Table 46: Control Byte C1 Or C2 - WAGO 750-632 Manual

Proportional valve module for wago-i/o-system 750
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module

Table 45: Status Byte S0

Bit 7
REG=0
REG=1
Key
REG
REGCOM_UPSTREAM
ERR*
ERR_CH2 **
ERR_CH1 **
ERR_MOD **
*
The bit remains set until the cause of the error is remedied and the error is acknowledged.
Acknowledgement takes place at the positive edge of bits C0.PWR_EN or C1.PWR_EN.
**
The bit remains set until the cause of the error is remedied and the error is acknowledged.
Acknowledgement takes place at the positive edge of bits V1_Control1.PWR_EN or V2_Control1.PWR_EN.
The configuration of the control and status bytes (C1 or C2 and S1 or S2) is
identical for each channel.

Table 46: Control Byte C1 or C2

Bit 7
JOG_POS
Key
JOG_POS
JOG_NEG
DITHER
RSEL
SPL_EN
PWR_EN
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Bit 6
Bit 5
ERR
0
0: Register communication disabled
1: Register communication enabled
Internal parameter
0: No errors present.
1: The I/O module is in error condition.
The source of error is displayed in bits 0 ... 2.
The error code was transferred via the mailbox.
0: Channel 2 has no errors
1: Channel 2 has one or more errors.
0: Channel 1 has no errors.
1: Channel 1 has one or more errors
0: There are no errors.
1: There are one or more errors.
Control Byte C1 or C2
Bit 6
Bit 5
JOG_NEG
DITHER
This bit is only evaluated by the I/O module if SPL_EN=0.
1: Setpoint value specified by set up function, rising ramp
0: Setpoint value specified by set up function, hold value
This bit is only evaluated by the I/O module if SPL_EN=0.
1: Setpoint value specified by set up function, falling ramp
0: Setpoint value specified by set up function, hold value
0: Dithering is switched off
01: Dithering is switched on
10: Dithering is switched off
Select the ramps for increasing or decreasing target variable.
The bits select the values from a parameter table (SC_RCONF)
0: Value for current ramps is gathered from parameter SC_RISE/FALL1
1: Value for current ramps is gathered from parameter SC_RISE/FALL2.
2: Value for current ramps gathered from parameter SC_RISE/FALL3.
3: Value for current ramps gathered from parameter SC_RISE/FALL4.
0: Setpoint value specified by set up function
1: Setpoint value specified in process image
0: Output stage is switched off
1: Output stage is switched on
This bit also has an alternative function for acknowledging errors:
-
Failure of the 24 V supply
-
Error in the output stage: short circuit, wire break, overload, undervoltage
If the error is no longer present, the rising edge has the effect that all errors are acknowledged in the
K-Bus status byte.
Status Byte S0
Bit 4
Bit 3
0
0
ERR_CH2
REGCOM_UPSTREAM
Bit 4
Bit 3
RSEL
Process Image
Bit 2
Bit 1
ERR_CH1 ERR_MOD
Bit 2
Bit 1
0
SPL_EN
PWR_EN
65
Bit 0
Bit 0