Use in Hazardous Environments
Pos : 122.20 /Seri e 750 ( WAGO-I/O-SYSTEM)/Einsatz in Ex- Ber eichen/Bes ondere Bedingungen für den sicheren Ex-Betrieb g em. IEC- Ex-Zertifi kat TUN 14.0035 X_2014 @ 21\mod_1416995779884_21.doc x @ 169122 @ 3 @ 1
12.2.3
Special Conditions for Safe Use (IEC-Ex Certificate TUN
14.0035X)
1.
The modules of the WAGO-I/O-SYSTEM 750-*** have to been erected in
such a way, that corresponding to IEC 60079-15 a degree of protection of at
least IP 54 according to IEC 60529 is achieved.
2.
Measures have to been taken, external to the modules, to provide a transient
protection that ensures that the rated voltage, connected to the power supply
terminals, is not exceeded by more than 40 %.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted if no explosive atmosphere exists. This although applies for
the all switches, interfaces (Fieldbus, Ethernet, Serial) and the SD-card.
4.
The ambient temperature range is: 0 °C ≤ Tamb ≤ +60 °C
The ambient temperature range for modules with suffix extension /025-****
is: -20 °C ≤ Tamb ≤ +60 °C
Pos : 122.21 /D okumentati on allgemein/Gliederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
Version 1.3.0, valid from FW/HW-Version 01/01
Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-632/000-100

Table of Contents