4.2.2

Power Jumper Contacts/Field Supply

Pos : 35.1 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Vorsic ht/Vorsicht: Verl etz ungsgefahr durc h s charfkantige M ess er kontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
Pos : 35.2 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Mess er/Leis tungs kontakte 2 LK (Messer /Feder) - Ei nleitung @ 15\mod_1371721641099_21.doc x @ 123714 @ @ 1
The I/O module 750-632 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.
Pos : 35.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Mess er/F eder) - Abbildung (16-Kanal) @ 15\mod_1370866610582_21.doc x @ 122222 @ @ 1

Figure 4: Power Jumper Contacts

Pos : 35.4 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Mess er/Leis tungs kontakte 2 LK (Messer /Feder) - Legende @ 15\mod_1371721352500_21.doc x @ 123710 @ @ 1

Table 6: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Pos : 35.5 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Achtung/Achtung: M axi mal er Strom Leistungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos : 36 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Type
Spring contact
Potential transmission (U
Spring contact
Potential transmission (0 V) for field supply
Blade contact
Blade contact
Function
Potential feed-in (0 V) for field supply
Potential feed-in (U
v
Device Description
) for field supply
v
) for field supply