If a temperature of 97°C is overrun or underrun, then a warning diagnostic
message is generated.
If a temperature of 102°C is overrun or underrun, then a switch off
diagnostic message is generated.
Optionally, the internal temperature can be read in the ST_MODULE_TEMP
register via the mailbox.
10.5.5

Switching Outputs Back On

In order to switch the I/O module's outputs on again, proceed as follows:
1.
Set the PWR_EN bit to "0" for at least 100 ms.
2.
Set the PWR_EN bit back to "1".
If the error is remedied, then the READY bit is automatically set to "1". All bits in
the status byte of the I/O module are acknowledged. The LEDs for "Status
channel A" and "Status channel B" light up green. If the mailbox is enabled, a
diagnostic message is additionally generated.