32
Process Image
4.3
Process Data
4.3.1
Overview of Sensor Types
The following table serves as an overview of all supported sensor types
presented in standard format and in S5-FB250 format. The following sections
provide detailed information about the individual sensor types ordered by ID. The
information in the respective tables for resolution and measured values, as well
as the resulting raw value ranges are based on the manufacturer scaling.
Table 22: Process Data, Overview in Standard Format and S5-FB250 Format
Sensor
ID
type
0
Pt100
1
Ni100
2
Pt1000
3
Pt500
4
Pt200
5
Ni1000
6
Ni120
7
Ni1000
8
Ni1000
9
Ni1000
10
Pt1000
11
Pt100 *
12
13
Resistance
14
measuring
range 1
Resistance
15
measuring
range 2
* Firmware versions 02 and above
Manual
Version 1.2.0
Standard Measuring range
IEC 751
−200 °C ... 850 °C
DIN 43760
−60 °C ... 250 °C
IEC 751
−200 °C ... 850 °C
IEC 751
−200 °C ... 850 °C
IEC 751
−200 °C ... 850 °C
TK6180
−60 °C ... 250 °C
DIN 43760
Minco
−80 °C ... 260 °C
TK5000
(Landis +
−60 °C ... 250 °C
Staefa)
TK6180
−50 °C ... 150 °C
DIN 43760
TK5000
(Landis +
−50 °C ... 150 °C
Staefa)
IEC 751
−50 °C ... 150 °C
IEC 751
−50 °C ... 150 °C
Reserved for expansions
Reserved for expansions
–
0 Ohm ... 5 kOhm
–
0 Ohm ... 1.2 kOhm
WAGO-I/O-SYSTEM 750
Notation
Standard format
Resolu-
Raw value
tion
range
0.1 °C
−2000 ... 8500
0.1 °C
−600 ... 2500
0.1 °C
−2000 ... 8500
0.1 °C
−2000 ... 8500
0.1 °C
−2000 ... 8500
0.1 °C
−600 ... 2500
0.1 °C
−800 ... 2600
0.1 °C
−600 ... 2500
−5000 ...
0.01 °C
15000
−5000 ...
0.01 °C
15000
−5000 ...
0.01 °C
15000
−5000 ...
0.01 °C
15000
0.2 Ohm
0 ... 25000
0.05 Ohm
0 ... 24000
750-451 8 AI RTD
S5-FB250 format
Resolu-
Raw value
tion
range
0.5 °C
−400 ... 1700
0.5 °C
−120 ... 500
0.5 °C
−400 ... 1700
0.5 °C
−400 ... 1700
0.5 °C
−400 ... 1700
0.5 °C
−120 ... 500
0.5 °C
−160 ... 520
0.5 °C
−120 ... 500
0.05 °C
−1000 ... 3000
0.05 °C
−1000 ... 3000
0.05 °C
−1000 ... 3000
0.05 °C
−1000 ... 3000
4 Ohm
0 ... 1250
0.5 Ohm
0 ... 2400