WAGO-I/O-SYSTEM 750
750-469 2AI Thermocouple
4
Process Image
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules' process data in the process image depends
on the fieldbus coupler/controller used. Please take this information as well as the
particular design of the respective control/status bytes from the section "Fieldbus
Specific Design of the Process Data" included in the description concerning the
process image of the fieldbus coupler/controller used.
4.1
Standard Data Format
For the 750-469 module and its variations with standard data format, the
temperature values of the sensors are represented with a resolution of 1 digit per
0.1 °C within a word (16 bits). Thus, 0 °C corresponds to the numeric value
0x0000 and 100 °C to 0x03E8 (dec. 1000).
Table 16: Process Image 750-469, 750-469/003-000, type K, with broken wire diagn.
Temperature
°C
< -100.0
-100.0
0.0
100.0
200.0
300.0
400.0
500.0
1000.0
1200.0
1300.0
1370.0
> ca.1370.0
Broken wire
1)
Temperature values below 0 °C are represented in two's complement binary form.
Manual
Version 1.1.0
Numercial value
binary
'1111.1100.0001.1000'
'1111.1100.0001.1000'
'0000.0000.0000.0000'
'0000.0011.1110.1000'
'0000.0111.1101.0000'
'0000.1011.1011.1000'
'0000.1111.1010.0000'
'0001.0011.1000.1000'
'0010.0111.0001.0000'
'0010.1110.1110.0000'
'0011.0010.1100.1000'
'0011.0101.1000.0100'
'0011.0101.1000.0100'
'0111.1111.1111.1111'
Process Image
1)
hex.
dec.
0xFC18
-1000
0xFC18
-1000
0x0000
0
0x03E8
1000
0x07D0
2000
0x0BB8
3000
0x0FA0
4000
0x1388
5000
0x2710
10000
0x2EE0
12000
0x32C8
13000
0x3584
13700
> 0x3584
> 13700
0x7FFF
32767
27
Status-
LED
byte
Error
hex.
AI 1, 2
0x41
on
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x42
on