MCO 305 Design Guide
Application Settings
19-** Application Parameters
19-00 ...19-89 Application Parameters
Range
-2147483648 – 2147483647
(The real range seen at the LCP is defined by
LINKGPAR)
Function
The application parameters can be used to input
application specific data to the application program.
Application parameters are created via the
LINKGPAR command whereby it is possible to
specify parameter name as well as minimum and
maximum setting limits. See also description of
LINKGPAR.
Note: Application parameters are only visible and
accessible via LCP when created/defined in the
application program.
Syntax Example
LINKGPAR 1901 "name" 0 100000 0
/* Link par. 19-01 with LCP */
default setting
__ Parameter Reference __
[ ]
value for use in communication via serial communication port
®
MG.33.L4.02 – VLT
is a registered Danfoss trademark
19-90 .. 19-99 Read only Application
Parameters
Range
-2147483648 – 2147483647
(Range depends on the data linked to the read-out
parameter)
Function
The read only application parameters can be used
to read out additional internal process data and
application specific data from the application
program. Read only application parameters are
created via:
LINKSYSVAR command for internal process
data.
LINKGPAR command for application specific
data;
whereby it is possible to specify the parameter
name. See also description of LINKSYSVAR and
LINKGPAR.
Parameters 19-90 through 19-99 can be selected
as LCP display read outs via parameters 0-20
through 0-24.
Note: Read only application parameters are only
visible at LCP when created/defined in the
application program.
181