Danfoss MCO 305 Design Manual page 150

Hide thumbs Also See for MCO 305:

Advertisement

MCO 305 Design Guide
SETVLT
Summary
Syntax
Parameter
Description
Command Group
Cross Index
Syntax Example
SETVLTSUB
Summary
Syntax
Parameter
Description
Command Group
Cross Index
Syntax Example
150
__ Software Reference __
Sets a FC 300 parameter
SETVLT par v
par = parameter number
v
= parameter value
With the SETVLT command FC 300 parameters can be changed temporarily and
thus the configuration of the FC 300 can also be changed temporarily.
Since only integer values can be transmitted the parameter value to be transmitted
must be adjusted with the associated conversion index.
A list of the FC 300 parameters with the corresponding conversion index can be
found in the FC 300 manual.
NB!:
The parameter alterations are only stored in RAM. After power down the original
parameter values are restored.
PAR
GETVLT
/* change par. 3-03 "maximum reference" high to 60 Hz */
/* -Conversion index = -3 (Multiplied with 10³ during transmission) */
SETVLT 3-03 60000
Sets a FC 300 parameter with index number.
SETVLTSUB par indxno v
par
= parameter number
indxno
= index number
v
= parameter value
With the SETVLT commands FC 300 parameters can be changed temporarily and
thus the configuration of the FC 300 can also be changed temporarily, in this case
parameters with index numbers too.
Since only integer values can be transmitted the parameter value to be transmitted
must be adjusted with the associated conversion index.
A list of these parameters with the corresponding conversion index can be found in
the FC 300 manual.
NB!:
The parameter alterations are only stored in RAM. After power down the original
parameter values are restored.
PAR
GETVLTSUB
SETVLT 0-25 1 100
// sets index 1 of the par. 0-25 "Quick menu" to 100 "configuration"
®
MG.33.L4.02 – VLT
is a registered Danfoss trademark