Danfoss MCO 305 Design Manual page 100

Hide thumbs Also See for MCO 305:

Advertisement

MCO 305 Design Guide
COMOPTGET
Summary
Reads a Communication option telegram
Syntax
COMOPTGET no array
Parameter
array =
no =
Description
COMOPTGET reads from the Communication option buffer the no words and writes
them in the array 'array', starting with the first element.
Portability
Option
Communication
Parameters: Read and write parameters are not affected by the option board.
Option Function
NB!:
The parameters 9-15 and 9-16 have additionally to be set with the correct values.
Control data:
The function of Control word (CTW) and Main Reference (MRV) depends on the
setting of par. 33-82 Drive Status Monitoring; Status words (STW) and Main actual
value (MAV) is always active:
Process data:
PCD's 1 – 4 of PPO type 2/ 4 and PCD's 1 – 8 of PPO type 5 are not assigned a
parameter number by parameters 9-15 and 9-16 but are used as a free data area
which can be used in a APOSS program.
The command COMOPTGET is copying the data received on the communication
option into an array, where each array element contains one data word (16 bit).
The command COMOPTSEND is copying data from an array, where each array
element contains one data work (16 bit) into the send buffer on the communication
option, from where it is send via the network to the master.
Command Group
Communication option
Cross Index
COMOPTSEND
Program Sample
COM_OPT
COMOPTSEND
Summary
Writes in the Communication option buffer
Syntax
COMOPTSEND no array
Parameter
array =
no =
Description
COMOPTSEND writes in the Communication option buffer. In doing so the first 'no'
values are sent from the 'array'.
Portability
With built-in Communication option.
Communication
See command COMOPTGET
Option Function
Command Group
Communication option
Cross Index
COMOPTGET
Program Sample
COM_OPT
100
__ Software Reference __
the name of an array which must be at least the size of no
number of words to be read
CTW/MRV
STW/MAV
the name of an array which must be at least the size of 'no'
number of words to be sent
®
MG.33.L4.02 – VLT
is a registered Danfoss trademark
Parameter 33-82
"Enable MCO 305"
Disabled
Active
Parameter 33-82
"Disable MCO 305"
Active
Active