Installation position:
The maximum ambient temperature for CPU modules mounted on a top-hat rail is 50°C. The orientation in
which the device is fitted must be selected in such a way that cooling air can flow vertically through the ven-
tilation holes. The images show the correct (Fig. 8) and two incorrect installation positions (Figs. 9 & 10).
  Observe minimum clearance! Mounting must provide a clearance of 30 mm both above and below a
CX1000 device combination to ensure adequate ventilation of the base CPU module and the power supply
unit.
Correct installation position:
The high-performance CX1020 system generates a significant amount of heat, which is dissipated via a
passive ventilation system. This system requires the unit to be mounted correctly. Ventilation openings are
located at the top and bottom of the housing. The system therefore has to be installed horizontally. This
ensures optimum air flow.
    
Incorrect installation positions:
The CX1020 system must not be operated vertically on the top-hat rail. A vertical position would lead to
insufficient CPU ventilation, since the ventilation openings are located on the top and bottom of the housing.
Installation of the system on its side would also lead to inadequate ventilation.
7.2
Certifications
All products of the Embedded PC family are CE, UL and GOST-R certified. Since the product family is
continuously developed further, we are unable to provide a full listing here. The current list of certified
products can be found on the Embedded PC certificates web page or at www.beckhoff.com under Embedded
PC.
7.3
Support and Service
Beckhoff and their partners around the world offer comprehensive support and service, making available fast
and competent assistance with all questions related to Beckhoff products and system solutions.
Beckhoff's branch offices and representatives
Please contact your Beckhoff branch office or representative for local support and service on Beckhoff
products!
The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet
pages:
http://www.beckhoff.com
You will also find further documentation for Beckhoff components there.
CX1500-M510, CX1500-B510
NOTE
Version: 1.0
Appendix
179

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cx1500-b510Cx1500-b310

Table of Contents