Beckhoff CX1500-M510 Manual page 131

Canopen - bus interfaces for cx systems
Table of Contents

Advertisement

Index
Sub-index Name
0x1801
0
1
2
3
4
5
The second transmit PDO is provided by default for analog inputs, and is configured for event-driven
transmission (transmission type 255). Event-driven mode must first be activated (see object 0x6423),
otherwise the inputs can only be interrogated (polled) by remote transmission request (RTR).
Communication parametersfor the 3rd TxPDO
for the 3rd TxPDOCommunication parameters
CX1500-M510, CX1500-B510
Type
Number of
Unsigned8 ro
elements
COB-ID
Unsigned32 rw
Transmissi
Unsigned8 rw
on Type
Inhibit Time Unsigned16 rw
CMS
Unsigned8 rw
Priority
Group
Event
Unsigned16 rw
Timer
Version: 1.0
Attribute
Mapping
N
N
N
N
N
N
Product overview
Default
Meaning
value
5
Communica
tion
parameters
for the
second
transmit
PDO. Sub-
index 0:
number of
following
parameters
0x0000028
COB-ID
0 + Node-
(Communic
ID
ation Object
Identifier)
TxPDO1
255
Transmissi
on type of
the PDO
0
Repetition
delay [value
x 100 µs]
-
Present for
reasons of
backwards
compatibilit
y, but not
used.
0
Event-
Timer
131