Misoperation prevention and parameter setting restriction

4.16 Misoperation prevention and parameter setting restriction

Purpose
To limit reset function
To trip when PU is disconnected
To stop from PU
To prevent parameter rewrite
To prevent reverse rotation of the
motor
To display necessary parameters
To restrict parameter using
password
To control parameter write by
communication

4.16.1 Reset selection/disconnected PU detection/PU stop selection (Pr.75)

You can select the reset input acceptance, disconnected PU (FR-PU07) connector detection function and PU stop
function.
Parameter
number
Reset selection/
75
disconnected PU detection/
PU stop selection
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)
The Pr.75 value can be set any time. Also, if parameter (all) clear is executed, this setting will not return to the initial value.
Pr.75
Reset Selection
Setting
0
Reset input normally enabled
Reset input is enabled only when the
1
fault occurs.
2
Reset input normally enabled
Reset input is enabled only when the
3
fault occurs.
14
(initial
Reset input normally enabled
value)
Reset input is enabled only when the
15
fault occurs.
16
Reset input normally enabled
Reset input is enabled only when the
17
fault occurs.
(1) Reset selection
 You can select the enable condition of reset function (RES signal, reset command through communication) input.
 When Pr.75 is set to any of "1, 3, 15, 17", a reset can be input only when the drive unit is tripped.
NOTE
 When the reset signal (RES) is input during operation, the motor coasts since the drive unit being reset shuts off the
output.
 When reset is performed, cumulative values of electronic thermal O/L relay, regenerative brake duty are cleared.
 The reset key of the PU is only valid when the drive unit is tripped, independently of the Pr.75 setting.
178
Reset selection/
disconnected PU
detection/PU stop selection
Parameter write disable
selection
Reverse rotation
prevention selection
Display of applied
parameters
Password function
EEPROM write selection
Name
Initial value
If the PU is disconnected, operation
will be continued.
When the PU is disconnected, the drive
unit trips.
If the PU is disconnected, operation
will be continued.
When the PU is disconnected, the drive
unit trips.
Parameter to set
Setting range
14
0 to 3, 14 to 17
Disconnected PU Detection
Pr.75
Pr.77
Pr.78
Pr.160
Pr.296, Pr.297
Pr.342
Description
For the initial value, reset always
enabled,without disconnected PU
detection, and with PU stop function are
set.
PU Stop Selection
Pressing
decelerates the motor to
a stop only in the PU operation
mode.
Pressing
decelerates the motor to
a stop in any of the PU, External and
Network operation modes.
Refer to page
178
181
182
182
183
208