Mitsubishi Electric FR-E700EX Instruction Manual page 239

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

4) Reverse operation
Increases the manipulated variable (rotation speed) if deviation X = (set point - measured value) is positive, and decreases
the manipulated variable if deviation is negative.
Set point
5) Forward operation
Increases the manipulated variable (rotation speed) if deviation X = (set point - measured value) is negative, and decreases
the manipulated variable if deviation is positive.
Set point
Relationships between deviation and manipulated variable (rotation speed)
Positive
Reverse action
Forward action
(3)
Connection diagram
Sink logic
Pr.128 = 20
Pr.182 = 14
Pr.190 = 15
Pr.191 = 14
Pr.192 = 16

The power supply must be selected in accordance with the power specifications of the detector used.

The used output signal terminal changes depending on the Pr.190 to Pr.192 (output terminal selection) setting.

The used input signal terminal changes depending on the Pr.178 to Pr.184 (input terminal selection) setting.

The AU signal need not be input.
[Heating]
+
X>0
Cold
X<0
-
Feedback signal
(measured value)
[Cooling]
+
X>0
Too cold
X<0
-
Feedback signal
(measured value)
Deviation
Negative
MCCB
Power supply
Forward rotation
Reverse rotation
Reverse rotation
Setting Potentiometer
(Set point setting)
AC1φ
200/220V 50/60Hz
Special operation and speed control
Deviation
Increase
Hot
Decrease
Measured value
Decrease
Hot
Increase
Deviation
Drive unit
Motor
U
R/L1
S/L2
V
M
W
T/L3
STF
STR
RH(X14)
∗3
SD
Upper limit
(FUP)RUN
∗2
∗2
(FDN)FU
Lower limit
10
2
5
SE
Output signal
common
4
∗4
(measured value) 4 to 20mA
0
24V
Power
∗1
supply
Set point
Measured value
Set point
Pump
P
2-wire type
3-wire type
Detector
-
+
+
-
+
(OUT)
(COM)
(24V)
4
237