Function assignment of external terminal and control

4.12.5 Output terminal function selection (Pr.190 to Pr.192)

You can change the functions of the open collector output terminal and relay output terminal.
Parameter
number
190
RUN terminal function
selection
191
FU terminal function
selection
192
A,B,C terminal function
selection
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)

The setting values "93" and "193" are available only in Pr.190 and Pr.191.

The setting values "68" and "168" are valid only when used with FR-E7DS. (For the details, refer to the Instruction Manual of FR-E7DS.)
...... Specifications differ according to the date assembled. Refer to page 316 to check the SERIAL number.
(1) Output signal list
 You can set the functions of the output terminals.
 Refer to the following table and set the parameters: (0 to 99: positive logic, 100 to 199: negative logic)
Setting
Signal
Positive
Negative
logic
logic
0
100
RUN
1
101
SU
3
103
OL
4
104
FU
7
107
RBP
8
108
THP
11
111
RY
12
112
Y12
13
113
Y13
144
Name
Open
collector
output
terminal
Relay
output
terminal
Function
Speed
control
Drive unit running
Position
control
Speed
control
Up to speed
Position
control
Overload alarm
Output while torque limit function is activated.
Output when the rotation speed reaches the speed
Rotation speed detection
set in Pr.42 (Pr.43 for reverse rotation).
Regenerative brake pre-
Output when 85% of the regenerative brake duty set
alarm
in Pr.70 is reached.
Output when the electronic thermal value reaches
Electronic thermal O/L
85% of the trip level. (Electronic thermal relay
relay pre-alarm
function protection (E.THT/E.THM) activates, when
the value reached 100%.)
Output when reset process is completed (when the
drive unit can be started by switching the start signal
Drive unit operation ready
ON or while it is running) after power-ON of the drive
unit.
Output when the output current is the Pr.150 setting or
Output current detection
higher for longer than the time set in Pr.151.
Output when the output power is the Pr.152 setting or
Zero current detection
lower for longer than the time set in Pr.153.
Initial
Initial signal
value
RUN (drive unit
0
runnning)
FU (rotation speed
4
detection)
99
ALM (fault output)
Operation
Output when the drive unit starts running
upon turning ON of the start signal.
Turned OFF when the drive unit performs
deceleration stop and zero speed control
or servo lock is activated.
Same operation as that of the RY2 signal
Output when the rotation speed is reached
to the set speed.

Setting range
0, 1, 3, 4, 7, 8, 11 to 16, 21,
24 to 26, 33, 36, 38, 47, 55, 56,
60, 61, 63, 64, 68, 90, 91, 93,
95, 96, 98, 99, 100, 101, 103,
104, 107, 108, 111 to 116, 121,
124 to 126, 133, 136, 138, 147,
155, 156, 160, 161, 163, 164,
168, 190, 191, 193, 195, 196,
198, 199, 9999
Refer
Related
to
parameter
page

147
Pr.41, Pr.870
149
Pr.22, Pr.48,
111
Pr.156, Pr.157
Pr.42, Pr.43,
149
Pr.870
Pr.70
136
Pr.9
130

147
Pr.150, Pr.151
150
Pr.152, Pr.153
150