Main Circuit Terminal Specifications; Specification Of Main Circuit Terminal; Terminal Arrangement Of The Main Circuit Terminal, Power Supply And The Motor Wiring - Mitsubishi Electric FR-E700EX Instruction Manual

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

2.2

Main circuit terminal specifications

2.2.1

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Drive unit output
P/+, PR
Brake resistor connection
P/+, N/-
Brake unit connection
P/+, P1
DC reactor connection
Earth (Ground)
2.2.2
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
Three-phase 200V class
FR-E720EX-0.1K to 0.75K
N/-
R/L1 S/L2 T/L3
Power supply
NOTE
 Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the drive unit. Doing so will damage the drive unit.
 Connect the motor to U, V, W. Turning ON the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
Connect to the commercial power supply.
Keep these terminals open when using the high power factor converter (FR-HC2) or
power regeneration common converter (FR-CV).
Connect a three-phase squirrel-cage motor.
Connect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and
PR.
(The brake resistor can not be connected to the 0.1K or 0.2K.)
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV)
or high power factor converter (FR-HC2).
Remove the jumper across terminals P/+ and P1 and connect a DC reactor.
For earthing (grounding) the drive unit chassis. Must be earthed (grounded).
Jumper
P/+
PR
M
Motor

Main circuit terminal specifications

Description
FR-E720EX-1.5K to 3.7K
Jumper
N/- P/+
R/L1 S/L2 T/L3
PR
Power supply
2
M
Motor
15