Position control
4.5.6

Stopper control function (Pr.512 to Pr.515, X29 signal)

Under stopper control, the motor outputs holding torque to press a workpiece to a mechanical stopper for more
accurate positioning. This function enables a stable stop for positioning.
Parameter
Name
number
Stopper control function
512
selection
513
Stopper control torque limit
Stopper control switchover
514
position lower 4 digits
Stopper control switchover
515
position upper 4 digits
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)
(1) Stopper control by the X29 signal (Pr.512 = "1", Pr.513, X29 signal)
 When the X29 signal (stopper control switchover signal) is assigned to the input terminal, the Pr.513 setting is applied and
E.OLT is disabled.
To input the X29 signal, set "29" in any of Pr.178 to Pr.184 (input terminal function selection) to assign the function to a
terminal.
 Stopper control by the X29 signal is compatible with both speed control or position control.
 When Pr.513 Stopper control torque limit has been activated and has stopped the motor, E.OLT does not occur, but the
electronic thermal O/L relay is activated. Thus, performing stopper control at a high load for a long time may cause the
motor overload trip fault (E.THM) or drive unit overload trip fault (E.THT).
 The Pr.513 setting must be 80% or lower to prevent the motor from overheating.
SON signal
ON
RH signal
RL signal
X29 signal
ON
STF signal
STR signal
Torque limit
Pr.22
Rotation
speed
0
Example of speed control
102
Initial
value
0
40%
0
0
ON
ON
ON
ON
ON
Pr.513
Pr.22
Stopper
control
Setting
range
Set a condition to apply the Pr.513 setting, not to activate, and
E.OLT.
0
Stopper control disabled
When the X29 signal is turned ON (speed control, position
1
control)
Under position control,
Current position [before electronic gear]  Pr.515 + Pr.514
10
or
Current position [before electronic gear]  -(Pr.515 + Pr.514 )
Under position control,
11
Current position [before electronic gear]  Pr.515 + Pr.514
Under position control,
12
Current position [before electronic gear]  -(Pr.515 + Pr.514 )
0 to 200% Set the torque limit value under stopper control.
0 to 9999 When the current position [before the electronic gear] enters
the range set by Pr.512 under position control, the torque limit
operation is activated according to the Pr.513 setting.
0 to 9999
SON signal
ON
RH signal
RM signal
ON
STF signal
X29 signal
Torque limit
Rotation
speed
Position
Time
command
Position
Example of position control
Description
ON
ON
ON
ON
Pr.22
Pr.513
Stopper
control
Pressing
Current positon
Time
Time