4.13.2 Monitor display selection of DU/PU and terminal FM

(Pr.52, Pr.54, Pr.170, Pr.171, Pr.268, Pr.430, Pr.563, Pr.564)
The monitor to be displayed on the main screen of the control panel and parameter unit (FR-PU07) can be selected.
In addition, signal to be output from the terminal FM (pulse train output) can be selected.
Parameter
Name
number
DU/PU main display data
52
selection
FM terminal function
54
selection
170
Watt-hour meter clear
171
Operation hour meter clear
Monitor decimal digits
268
selection
430
Pulse monitor selection
Energization time carrying-
563
over times
Operating time carrying-over
564
times
The above parameters can be set when Pr.160 Extended function display selection = "0". (Refer to page 182)
 This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr.77 Parameter write selection
Monitor display and monitor output signal
Initial value
Setting range
0
0, 5, 8 to 12, 14, 19,
(rotation speed
20, 23 to 31, 36, 37,
(output
52 to 55, 61, 62, 100
frequency))
1
1 to 3, 5, 8 to 12, 14,
(rotation speed
21, 24, 36, 37, 52, 53,
(output
61, 62
frequency))
0
10
9999
9999
9999
0, 9999
0
9999
1
9999
4
5
100
101
9999
102
103
104
105
9999
0 to 65535
0
(reading only)
0 to 65535
0
(reading only)
Description
Select the monitor to be displayed on the
operation panel and parameter unit.
Refer to the following table for monitor
description.
Select the monitor output to terminal FM.
Set "0" to clear the watt-hour meter
monitor.
Sets the maximum value for the
monitoring from communication to
9999kWh.
Sets the maximum value for the
monitoring from communication to
65535kWh.
Set "0" in the parameter to clear the
operation time monitor.
Setting 9999 does not clear.
Displayed as integral value
Displayed in 0.1 increments.
No function
The lower 4 digits of the droop pulse [after
the electronic gear] is displayed.
The upper 4 digits of the droop pulse
[after the electronic gear] is displayed.
The lower 4 digits of the position
command [before the electronic gear] is
displayed.
The upper 4 digits of the position
command [before the electronic gear] is
displayed.
The lower 4 digits of the current position
[before the electronic gear] is displayed.
The upper 4 digits of the current position
[before the electronic gear] is displayed.
The lower 4 digits of the droop pulse
[before the electronic gear] is displayed.
The upper 4 digits of the droop pulse
[before the electronic gear] is displayed.
The rotation speed (output frequency)
monitor is displayed.
The numbers of cumulative energization
time monitor exceeded 65535h is
displayed. (Reading only)
The numbers of operation time monitor
exceeded 65535h is displayed. (Reading
only)