Monitor display and monitor output signal
(1) Monitor description list (Pr.52)
 Set the monitor to be displayed on the operation panel and parameter unit (FR-PU07) in Pr.52 DU/PU main display data
selection.
 Set the monitor to be output to the terminal FM (pulse train output) in Pr.54 FM terminal function selection.
 Refer to the following table and set the monitor to be displayed. (The monitor marked
Types of Monitor
Rotation speed
1r/min
(Output frequency)
(0.01Hz)
Output current
0.01A
Output voltage
Fault display
Speed setting
1r/min
(frequency setting
(0.01Hz)
value)
Converter output
voltage
Regenerative brake
0.1%
duty
Electronic thermal
relay function load
0.1%
factor
Output current peak
0.01A
value
Converter output
voltage peak value
Output power
0.01kW
Input terminal status
Output terminal
status
Position pulse
Cumulative
energization time 
Reference voltage
output
Actual operation time
, 
Motor load factor
0.1%
156
Pr.52 Setting
Operation
PU
Unit
Panel
Main
LED
Monitor
0/100
0/100
0.1V
0/100
0/100

5

0.1V
8

9

10

11

0.1V
12

14


19
1h
20
1h
23
24
Terminal FM
Pr.54 (FM)
Full Scale
Setting
Value
1
Pr.55
2
Pr.56
3
400V
5
Pr.55
8
400V
9
Pr.70
10
100%
11
Pr.56
12
400V
Rated drive unit
14
power
2
21
24
200%
cannot be selected.)
Description
Displays the drive unit rotation speed (drive
unit output frequency)
Displays the drive unit output current
effective value.
Displays the drive unit output voltage.
Displays 8 past faults individually.
Displays the set speed (frequency).
Displays the DC bus voltage value.
Brake duty set in Pr.30, Pr.70
Displays the thermal cumulative value on
the assumption that the thermal operation
level is 100% (Larger thermal between the
motor thermal and transistor thermal). 
Holds and displays the peak value of the
output power monitor.
(Cleared at every start)
Holds and displays the peak value of the
DC bus voltage value.
(Cleared at every start)
Displays the power on the drive unit output
side
Displays the input terminal ON/OFF status
on the PU. (Refer to page 159 for DU
display)
Displays the output terminal ON/OFF
status on the PU. (Refer to page 159 for DU
display)
Displays the position within one revolution
of the motor.
One revolution of the motor is 5120.
Adds up and displays the energization time
after drive unit shipment.
You can check the numbers of the monitor
value exceeded 65535h with Pr.563.
Terminal FM:
Output 1440pulse/s
Adds up and displays the drive unit
operation time.
You can check the numbers of the monitor
value exceeded 65535h with Pr.564.
Can be cleared by Pr.171. (Refer to page 160)
Displays the torque in percentage on the
assumption that the rated motor torque is
100%.
Monitor value = torque / motor rating
torque
100 [%]