Connection of stand-alone option unit

The drive unit accepts a variety of stand-alone option units as required.
Incorrect connection will cause drive unit damage or accident. Connect and operate the option unit carefully in accordance
with the corresponding option unit manual.
2.4.1
Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)
(0.4K or higher)
Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor is made to run by the load, quick
deceleration is required, etc. Connect a dedicated brake resistor to terminal P/+ and PR.
(For the locations of terminal P/+ and PR, refer to the terminal block layout (page 15).)
Set parameters below.
Connected brake resistor
MRS type, MYS type
MYS type
(used at 100% torque / 6%ED)
FR-ABR
NOTE
The brake resistor connected should only be the dedicated brake resistor.
FR-E720EX-0.4K, 0.75K
Connect the brake resistor across terminals P/+ and PR. Connect the brake resistor across terminals P/+ and PR.
Brake resistor
 Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
Pr.30 Regenerative function selection
Setting
0 (initial value)
1
1
Jumper
Terminal P/+
Terminal PR
Connection of stand-alone option unit
Pr.70 Special regenerative brake duty
6%
10%
FR-E720EX-1.5K to 3.7K
Terminal PR
Brake resistor
Setting
136
Refer to page
Jumper
Terminal P/+
27
2