Drive Unit Placement - Mitsubishi Electric FR-E700EX Instruction Manual

Sensorless servo drive unit, applied
Hide thumbs Also See for FR-E700EX:
Table of Contents

Advertisement

Installation of the drive unit and enclosure design
1.4.3

Drive unit placement

(1) Installation of the drive unit
Enclosure surface mounting
Remove the front cover and wiring cover to fix the drive unit to the surface.
FR-E720EX-0.1K to 0.75K
Front cover
NOTE
 When encasing multiple drive units, install them in parallel as
a cooling measure.
 Install the drive unit vertically.
(2) Clearances around drive unit
To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the drive unit. At least the
following clearances are required under the drive unit as a wiring space, and above the drive unit as a heat dissipation space.
Surrounding air temperature and humidity
Measurement
Temperature: -10 C to +50 C
Humidity: 90% RH or less
Leave enough clearances and
take cooling measures.
(3) Drive unit mounting orientation
Mount the drive unit on a wall as specified. Do not mount it horizontally or any other way.
10
Wiring cover
Measurement
position
Drive
5cm
5cm
unit
5cm
position
*
FR-E720EX-1.5K to 3.7K
Front cover
Clearances (front)
10cm or more
1cm
1cm
or more
or more
*
*
10cm or more
When using the drive units at the
surrounding air temperature of 40 C
or less, the drive units can be installed
without any clearance between them
(0cm clearance).
When surrounding air temperature
exceeds 40 C, clearances between
the drive units should be 1cm or more.
Wiring cover
Clearances (side)
Drive
1cm
unit
or more