Safety Integrated Basic Functions
10.10 Commissioning the "STO", "SBC" and "SS1" functions
No.
Parameter
6
p9620 = "fast DI
on CU"
Terminal "EP"
7
p9650 = "Value"
8
p9651 = "Value"
9
p9658 = "Value"
10
p9659 = "Value"
11
p9762 = "Value"
p9763 = "Value"
712
Description/comments
Set terminals for "Safe Torque Off (STO)".
Wire terminal "EP" (enable pulses) on the Motor Module.
Control Unit monitoring channel:
By appropriately interconnecting BI: p9620 for the individual drives, the following is possi-
ble:
Selecting/deselecting the STO
Grouping the terminals for STO
Motor Module monitoring channel:
By wiring the "EP" terminal accordingly on the individual Motor Modules, the following is
possible:
Selecting/deselecting the STO
Grouping the terminals for STO
Note:
The STO terminals must be grouped identically in both monitoring channels.
Set F-DI changeover tolerance time.
F-DI changeover tolerance time on Control Unit
The parameter is not changed until safety commissioning mode has been exited (i.e. when
p0010 ≠ 95 is set).
Due to the different runtimes in the two monitoring channels, an F-DI changeover (e.g.
selection/deselection of STO) does not take immediate effect. After an F-DI changeover,
dynamic data is not subject to a data cross-check during this tolerance time.
Debounce time for the fail-safe digital inputs to control STO/SBC/SS1.
Set transition period from STOP F to STOP A.
STOP F is the stop response that is initiated when the data cross-check is violated as a
result of fault F01611 or F30611 (SI: Defect in a monitoring channel). STOP F normally
triggers "No stop response".
After the parameterized time has expired, STOP A (immediate safety pulse inhibit) is trig-
gered by the fault F01600 or F30600 (SI: STOP A triggered).
The default setting for p9658 is 0 (i.e. STOP F immediately results in STOP A).
Time for carrying out forced dormant error detection and testing the safety switch-off paths.
After this time has expired, the user is requested to test the switch-off paths as a result of
alarm A01699 (SI CU: Necessary to test the switch-off signal paths) (i.e. select/deselect
STO).
The commissioning engineer can change the time required for carrying out the forced
checking procedure and testing the safety switch-off paths.
Set the new Safety password.
Enter a new password.
Confirm the new password.
The new password is not valid until it has been entered in p9762 and confirmed in p9763.
As of now, you must enter the new password in p9761 so that you can change Safety
parameters.
Changing the Safety password does not mean that you have to change the checksums.
Function Manual, 11/2017, 6SL3097-4AB00-0BP5