Profibus-Based Diagnostics - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System response - reading out diagnostics data
The converter can request diagnostics data via "Read data set" (detailed information is
provided in the PROFINET-IO specification (http://www.profibus.com)).
Example:
For example, a read record with index 0x800C can be used to read out diagnostics data from
specific sub slots. The following rules apply as example:
● 1 message block
if, at this drive object (one or several) faults of the same message class are identified
● n messages
if, at this drive object, n faults of different message classes are identified
Note
If a fault is active on the CU drive object, then this fault is propagated to all of the drive
objects associated with the CU. This fault can therefore be read out at each drive object.
11.1.5.2

PROFIBUS-based diagnostics

For communication via PROFIBUS, in the case of fault the following diagnostics data is
output:
● Standard diagnostics (Page 770)
● Identifier-related diagnostics (Page 771)
● Status messages/module status (Page 771)
● Channel-related diagnostics (Page 772)
● Data sets DS0/DS1 and diagnostics alarm (Page 773)
Message structure
The following applies if a message contains all of the specified diagnostics data:
● Standard diagnostics
Is always located at the beginning of the message.
● Data sets DS0/DS1 and diagnostics alarm
Is always located at the end of the message. This message part is always slot-specific.
The actual state of the slot responsible for the message is always transferred in the
message.
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.1 Communication according to PROFIdrive
Communication
769

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents