Error
Meaning
value
0x07
Description element cannot be
changed.
0x09
No description data available.
0x10
Read job will not be executed.
0x0B
No operating priority.
0x0F
No text array exists.
0x11
Request cannot be executed due to
operating status.
0x14
Illegal value.
0x15
Response too long.
0x16
Illegal parameter address.
0x17
Illegal format.
0x18
Number of values inconsistent.
0x19
Drive object does not exist.
0x20
Parameter text cannot be changed
0x21
Service not supported.
0x65
Parameter presently deactivated.
0x6B
Write access for the enabled control-
ler.
0x6C
Parameter %s [%s]: Unknown unit.
0x6D
Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
0x6E
Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
0x6F
Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
0x70
Parameter %s [%s]: Write access
only in the quick commissioning
mode (p0010 = 1).
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.1 Communication according to PROFIdrive
Remark
Modification access to a description element that cannot be
changed.
Access to a description that does not exist (the parameter
value exists).
The read request is refused because know-how protection is
active.
Modification access with no operating priority.
Access to a text array that does not exist (the parameter
value exists).
Access is temporarily not possible for unspecified reasons.
Modification access with a value that is within the limits but
is illegal for other permanent reasons (parameter with de-
fined individual values).
The length of the present response exceeds the maximum
transfer length.
Illegal or unsupported value for attribute, number of ele-
ments, parameter number, subindex or a combination of
these.
Write request: Illegal or unsupported parameter data format.
Write request: A mismatch exists between the number of
values in the parameter data and the number of elements in
the parameter address.
You have attempted to access a drive object that does not
exist.
Illegal or unknown request ID
You have tried to access a parameter that, although availa-
ble, does not currently perform a function (e.g. n control set
and access to a V/f control parameter).
Write access is possible while the device is in the "Controller
enable" state.
Pay attention to the parameter attribute "changeable" in the
SINAMICS S120/S150 List Manual (C1, C2, U, T).
Communication
Additional
info
Subindex