Resonance Damping - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

V/f control (vector control)

6.4 Resonance damping

6.4
Resonance damping
The resonance damping function dampens active current oscillations that can occur under
no-load conditions. Resonance damping is active in a range between 5% and 90% of the
rated motor frequency (p0310), but only up to 45 Hz.
Figure 6-6
Note
Maximum frequency resonance damping
When p1349 = 0, the changeover limit is automatically set to 95% of the rated motor
frequency, but only up to a maximum of 45 Hz.
Function diagrams (see SINAMICS S120/S150 List Manual)
• 6310
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• r0066
• r0078
• p0310[0...n]
• p1338[0...n]
• p1339[0...n]
• p1349[0...n]
306
Resonance damping
Vector control - Resonance damping and slip compensation
CO: Output frequency
CO: Torque-generating actual current value
Rated motor frequency
V/f mode resonance damping gain
V/f mode resonance damping filter time constant
Maximum frequency
Function Manual, 11/2017, 6SL3097-4AB00-0BP5