Vector control
5.17 Flying restart
Note
Parameter p1203 has no effect on the fast flying restart. Parameter p1202 (flying restart
detection current) can be used to tune the fast flying restart.
Note
Detection current must not become too small
If the drive is operated well into the field weakening or with filters or long cables, the
detection current may become too small with the fast flying restart (F07330).
In this case, set the detection current (p1202) to values > 30%.
Fast flying restart with voltage acquisition
The time for the connection to a rotating induction motor can be shortened when the terminal
voltage of the motor is measured. This requires that a VSM module is connected (see
Chapter "Voltage Sensing Module (Page 279)").
1. Select the voltage measurement for the fast flying restart: p0247.5 = 1.
2. Activate the flying restart: p1200 > 0.
The following status bits indicate the characteristic of the flying restart:
– For V/f control: r1204.15
– For vector control: r1205.18, r1205.19, r1205.20
Note
If the measured voltage amplitude undershoots the 1% limit of the converter rated voltage,
the flying restart with voltage measurement is deactivated and the rotating frequency sought.