Receiving data
The sent telegrams of all nodes are simultaneously available at the SINAMICS Link. Each
telegram has a length of 32 PZD. Each telegram has a marker of the sender. You select
those PZD that you want to receive for the relevant node from all telegrams. You can
process a maximum of 32 PZD.
Note
If you have not deactivated the evaluation of bit 10 with p2037 = 2, the first word of the
receive data (PZD 1) must be a control word, where bit 10 = 1 is set.
In this example, Control Unit 2 receives selected data from the telegram of Control Unit 1.
Proceed as follows to receive data:
1. In parameter p8872[0...31] enter the address of the node for which you want to read one
or more PZDs (e.g. p8872[3] = 1 → from node 1, read in PZD 4, p8872[15] = 0 → do not
read in PZD 16).
2. After setting the parameters, using parameter r2050[0...31] or r2060[0...31] you can read
out the values.
Table 11- 58 Receive data for Control Unit 2
From the sender
Transfer
Tel. word
1)
from
p8871[x]
p2051[0]
0
p2061[1]
1
2
p2061[3]
3
4
p2051[5]
5
p2051[4]
6
p2061[5]
7
8
p2061[6]
9
10
p2051[7]
11
p2051[8]
12
p2061[9]
13
14
-
15
...
...
-
31
Tel.word = telegram word
1)
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Address
Receive buffer
p8872[x]
p8870[x]
1
PZD 1
1
PZD 2
1
PZD 3
1
PZD 4
1
PZD 5
1
PZD 6
1
PZD 7
1
PZD 8
1
PZD 9
1
PZD 10
1
PZD 11
1
PZD 12
1
PZD 13
1
PZD 14
1
PZD 15
0
PZD 16
...
...
0
PZD 32
11.6 Communication via SINAMICS Link
Receiver
Data transferred in
r2050[x]
r2060[x]
Parameter Contents
0
-
r0899
-
1
r0061[0]
-
r0061[0]
-
3
r0080
-
5
-
r2131
6
-
r0899
-
7
r0061[0]
-
-
9
r0080
-
11
-
r2131
12
-
r2138
-
13
r0046
-
15
-
0
...
...
...
31
0
0
Communication
ZSW1
Actual speed value part 1
Actual speed value part 2
Actual torque value part 1
Actual torque value part 2
Actual fault code
ZSW1
Actual speed value part 1
Actual speed value part 2
Actual torque value part 1
Actual torque value part 2
Actual fault code
Control word, faults/alarms
Missing enables part 1
Missing enables part 2
Empty
...
-
895