Note
Under the condition that the drive system was commissioned with STARTER and no
PROFIdrive telegram was activated, the infeed can be switched on by issuing an enable
signal at the EP terminals and a positive signal edge at OFF1 (p0840).
Switching off the Active Line Module
The Active Line Module is switched off by the same procedure used to switch it on, but in the
reverse order. However, there is no precharging at switch off.
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.
This allows the attached drives to be braked in a controlled manner. Before the infeed is
switched off, the drives connected to the DC link should be in pulse inhibit mode.
Control and status messages
Table 2- 2
Active Infeed open-loop control
Signal name
ON/OFF1
OFF2
Enable operation
Disable motor operation
Inhibit regenerating
Acknowledge fault
Master control by PLC
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Internal control
Binector input
word
STWAE.0
p0840 ON/OFF1
STWAE.1
p0844 1 OFF2 and p0845 2
OFF2
STWAE.3
p0852 Enable operation
STWAE.5
p3532 Disable motor operation
STWAE.6
p3533 Inhibit regenerating
STWAE.7
p2103 1 Acknowledge or p2104
2 Acknowledge or p2105
3 Acknowledge
STWAE.10
p0854 Master control by PLC
2.1 Active Infeed
Display of internal
PROFIdrive
control word
telegram 370
r0898.0
E_STW1.0
r0898.1
E_STW1.1
r0898.3
E_STW1.3
r0898.5
E_STW1.5
r0898.6
E_STW1.6
r2138.7
E_STW1.7
r0898.10
E_STW1.10
Infeed
37