Servo control
4.10 V/f control
1. Check the requirements for V/f control.
– First commissioning has been carried out:
– First commissioning has not been carried out:
2. Set the rated motor speed via parameter p0311.
3. Activate V/f control with the parameter setting of p1317 = 1.
Note
Automatic activation of additional functions
With p1317 = 1, the following functions are also activated automatically:
• Resonance damping (p1338)
• Vdc controller (p1240, p1244, p1248, p1250)
• Limitation of the up ramp as a result of M, P and I limits
• The ramp-function generator is stopped as soon as the current limit p0640 is
4. Issue the enable signals for operation.
5. Enter the speed setpoint.
138
The parameters for V/f control have been initialized with appropriate values.
The following relevant motor data must be checked and corrected:
r0313 Motor pole pair number, actual (or calculated)
p0314 Motor pole pair number
p1318 V/f control ramp-up/ramp-down time
p1319 V/f control voltage at zero frequency
p1326 V/f control programmable characteristic frequency 4
p1327 V/f control programmable characteristic voltage 4
p1338[0...n] V/f mode resonance damping gain
p1339[0...n] V/f mode resonance damping filter time constant
p1349[0...n] V/f mode resonance damping maximum frequency
In order to obtain a pure diagnostic mode without any influence on actual values, the
resonance damping must be deactivated (p1338 = 0)
exceeded.