Avaya S8700 Manual page 138

Installing forip connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

138
Installing the S8700 IP Connect
5
Make cross-connections for each emergency trunk/emergency station pair.
The 808A is connected to the Main Distribution Frame (MDF) by means of a B25A
cable.
the connections at the trunk/auxiliary field for a telephone used only for emergency
transfer.
''Connections for Telephone Used for Emergency Transfer and as Normal Extension'' on
page 142
emergency transfer as well as a normal extension.
On the trunk identification label at the bottom of the panel, record the trunk line,
6
extension, and location for each circuit.
7
To each telephone designated as an emergency terminal, attach a label identifying it as
such. The labels are provided with the unit.
8
Check for normal operation as follows:
If all of the above conditions are not met, remove the panel from service and replace it
with a new panel.
9
Check for transfer operation as follows:
If all of the above conditions are not met, remove the panel from service and replace it
with a new panel.
.
Trunk/Test Switches
Switch Number
1
2
3
4
5
6
7
8
''Connections for Telephone Used for Emergency Transfer'' on page 141
shows the connections at the trunk/auxiliary field for a telephone used for
Place the test switch (switch 12) in NORMAL OPERATION.
Ensure the power supply is providing -48 VDC at 80 mA maximum. The power
LED should be ON.
Check wiring connections.
Verify there is dial tone on all emergency transfer sets.
Place the test switch (switch 12) in the ACTIVATED position.
The power LED should be OFF.
Verify there is dial tone on all emergency transfer sets.