Install Coupled Bonding Conductor; Connect The Power Cords - Avaya S8700 Manual

Installing forip connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

58
Installing the S8700 IP Connect

Install Coupled Bonding Conductor

The Coupled Bonding Conductor (CBC) provides mutual inductance coupling between the
CBC and the telephone cables exposed to lightning. The conductor can be a 10 AWG (#25) (6
2
mm
) wire tie wrapped to the exposed cables, a metal cable shield around the exposed cables, or
6 spare pairs from the exposed cable.
For a high-rise building, connect the CBC to an approved building ground on each floor. To
provide the coupled bonding protection:
1
Connect one end of the conductor to a telephone cable building entrance protector
ground that is connected to an approved ground.
2
Route the conductor next to the exposed telephone cables being protected until it reaches
the cross-connect nearest to the telephone system.
Position the non-exposed telephone cables at least 12 inches (30.5 cm) away from
3
exposed telephone cables whenever possible.
Terminate the other end to the single-point ground block provided for the telephone
4
system.

Connect the Power Cords

!
WARNING:
The AC power cord may connect to a properly rated power distribution unit, individual
AC power receptacles, or to a UPS. A rack-mounted UPS is recommended.
To connect the power cords:
1
Ensure the circuit breakers at the AC load center are OFF.
Connect the media gateway to the UPS or to an "unswitched" or "always on" electrical
2
outlet.
May 2002