Off-Premises Protection Requirements - Avaya S8700 Manual

Installing forip connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Connections to 24 Out-of-Building Telephones
2
4
10
12
Figure notes
1
Locally Engineered Cables and
Equipment
2
25-Pair Connector
Multi-Pair Protector Units (Primary
3
Protectors with Heat Coils or
Equivalent with Sneak Current
Protection)
4
B25A Cable (Male to Female)
Concentrator Cable (WP90929 List 1)
5
6
356A Adapter
7
Out-of-Building Wiring

Off-Premises Protection Requirements

Both building entrances require carbon block or equivalent protection and sneak current
protection. Protection can be provided by:
a 4-type protector, which is equipped with a heat coil
a 3-type protector plus a separate sneak current protector
The 4-type protector is the preferred device. For installations not using primary protection,
4-type protectors should always be used. When the 3-type protector is already installed, a
separate sneak current protector is required.
1
7
2
5
3
3
9
11
15
16
14
13
10
11
12
13
14
15
May 2002
Installing the S8700 IP Connect
4
6
4
6
4
crdf24o CJL 101396
8
Out-Of-Building Analog Telephones
Part of Main Distribution Frame
9
(MDF)
Station Side
Media Gateway Side
White Field
Purple Field
Cross-Connect Jumpers
Tip and Ring Wires
131
8

Advertisement

Table of Contents
loading

Table of Contents