Mounting the PBX

4
The PBX can be both wall-mounted or installed inside a 19" system cabinet.
2.1

PBX Location

When positioning the PBX take note of the location requirements in Tab. 4.1.
Tab. 4.1:
PBX location requirements
Location in general
Heat radiation
EMC
Convection
Environment
HBT_20321104_04/B0_en
Location requirement
• Easily accessible and with adequate lighting
• Do not position the PBX in direct sunlight or near heating sources
• Do not position the PBX in strong electromagnetic fields of radiation
(e.g. the radiation zone of an X-ray system, welding equipment etc.)
• Observe the clearance requirements above and below the PBX (see Fig. 4.1)
• Provide ventilation slots of approx. 600 cm
in cabinets
• Room temperature 5...35 °C
• Relative humidity 30.0.80%, non-condensing
ascom
Ascotel 2025/2045/2065
2
each at the top and bottom of built-
Mounting the PBX