2: P
S
RODUCT
PECIFICATIONS
Ambient Temperature, Input Voltage, I/O Simultaneous ON Ratio
When the FC6A Series MICROSmart is used in an ambient temperature of 45°C or higher, reduce the input voltage and I/O
utilization (simultaneous ON ratio: a%) according to the following diagrams. However, the following diagrams show the
temperature conditions when the FC6A Series MICROSmart is normally installed.
Note: Normally installed means the state in the diagram in "Normal Installation State" on page 3-1.
The usage conditions will also change according to the installation state. For details, see "Installation Location" on page 3-1.
■ Relay Output Type
(FC6A-D16R1CEE)
There are no usage restrictions for input and output I/O.
■ Transistor Output Type
(FC6A-D16P1CEE, FC6A-D16K1CEE, FC6A-D32P3CEE, FC6A-D32K3CEE)
Reduce the input voltage and I/O simultaneous ON ratio (a%) as shown in the following diagrams.
Input Voltage
(V DC)
28.8 V
24.0 V
0 V
0%
2-50
Input I/O
Ambient
Temperature 30°C
Ambient
Temperature 55°C
40%
60%
100%
FC6A S
MICROS
ERIES
Input Voltage
(V DC)
28.8 V
24.0 V
0 V
I/O Simultaneous
0%
ON Ratio (%)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
Output I/O
Ambient
Temperature 30°C
Ambient
Temperature 55°C
60%
80%
100%
I/O Simultaneous
ON Ratio (%)