Plus CPU module
■ Single-phase high-speed counter
The single-phase high-speed counter has three operation modes, the adding counter, the up/down selection reversible counter, and the dual-
pulse reversible counter.
The up/down selection reversible counter and the dual-pulse reversible counter which can count in both directions are supported.
This counter support 100 kHz (pulse width ≥ 5 μs) maximum pulse input and is capable of counting in a range from 0 to 4,294,967,295 (32 bits).
When the current value and preset value match or an overflow or underflow occurs, a comparison output turns on or an interrupt program is
executed.
This counter support resetting the current value by special internal relay reset input and reset input. When the reset input is turned on or
when the current value reset is executed, the current value becomes the reset value specified by special data registers. For details on the
reset input, see "Reset input" on page 5-28.
Counting Mode
Adding counter
Up/down selection
reversible counter
Dual-pulse reversible
counter
*1 The Plus 16-I/O type supports only reset input by special internal relay.
The Plus 32-I/O type can use I13 as an external reset input.
■ Two-phase high-speed counter
Group 1 to 2, group 3 to 4, group 5 to 6 two-phase high-speed counter
The two-phase high-speed counter counts with the phase difference between A-phase and B-phase pulse inputs.
These groups support 50 kHz maximum pulse input and are capable of counting in a range from 0 to 4,294,967,295 (32 bits).
Even higher speed counting is possible by specifying 2-edge count or 4-edge count.
When the current value and preset value match or an overflow or underflow occurs, a comparison output turns on or an interrupt program is
executed.
These groups support resetting the current value by special internal relay reset input and external reset input (Z-phase). When the reset
input is turned on or the current value reset is executed, the current value becomes the reset value specified by special data registers.
Counting Mode
2-edge count
4-edge count
*1 The Plus 16-I/O type supports only reset input by special internal relay.
The Plus 32-I/O type can use I13 as an external reset input.
Frequency
Group 2, 4, 6: 100 kHz
Group 1: 100 kHz
Group 3: 100 kHz
Group 5: 100 kHz
Group 1 to 2: 100 kHz
Group 3 to 4: 100 kHz
Group 5 to 6: 100 kHz
Group 1 to 2: 100 kHz
Group 3 to 4: 100 kHz
Group 5 to 6: 100 kHz
Frequency
Group 1 to 2: 50 kHz
Group 3 to 4: 50 kHz
Group 5 to 6: 50 kHz
Group 1 to 2: 25 kHz
Group 3 to 4: 25 kHz
Group 5 to 6: 25 kHz
FC6A S
MICROS
ERIES
Reset Input (Z-phase)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
5: F
UNCTIONS AND
Reset Input
I2
*1
I5
I2
*1
I5
I2
*1
I5
I2
*1
I5
I2
*1
I5
S
ETTINGS
5-19

Advertisement

Table of Contents
loading

Table of Contents