Maximum I/O Points When Using Expansion Interface Modules (Remote Master/Slave)
The following table gives the number of digital I/O points and analog I/O points when expansion interface modules (remote
master/slave) are connected to the Plus CPU module and the maximum number of expansion modules and cartridges are
connected to the system.
Digital I/O
Analog I/O

Cartridge Base Module

HMI Module

Node 0
Expansion Interface
Cartridges
Remote Master Module
(3 maximum)
(FC6A-EXM1M)
Expansion Interface
Remote Slave Module
(FC6A-EXM1S)
Node 1
Expansion Interface
Remote Slave Module
(FC6A-EXM1S)
(10 maximum)
Node 10
Maximum number of expansion modules:
Maximum number of expansion cartridges: 3
Notes:
I/O refresh time of the expansion interface remote master/slave modules is stored in D8618 (Refresh Time of Expansion Interface Remote
Master/Slave Modules Current Value) and D8619 (Refresh Time of Expansion Interface Remote Master/Slave Modules Maximum Value).
When the outputs status are changed in a shorter time than the I/O refresh time of the expansion interface remote master/slave modules,
the outputs status may be reflected to the actual outputs. Make sure that the outputs are controlled in a longer time than the I/O refresh
time of the expansion interface remote master/slave modules.
The expansion interface master/slave modules cannot be connected over the Ethernet switch.
I/O
Input
Output
Input
Output
Plus CPU Module
63
FC6A S
MICROS
ERIES
Expansion Modules (13 maximum)
Expansion Modules (15 maximum)
Expansion Modules (15 maximum)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
2: P
S
RODUCT
Maximum No. of I/O Points
2,044
2,044
511
258
Expansion Modules
(63 maximum)
PECIFICATIONS
2-119