IDEC MICROSmart FC6A Series User Manual page 55

Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

Ambient Temperature, Input Voltage, I/O Simultaneous ON Ratio
When the FC6A Series MICROSmart is used in an ambient temperature of 45°C or higher, reduce the input voltage and I/O
utilization (simultaneous ON ratio: a%) according to the following diagrams. However, the following diagrams show the
temperature conditions when the FC6A Series MICROSmart is normally installed.
Note: Normally installed means the state in the diagram in "Normal Installation State" on page 3-1.
The usage conditions will also change according to the installation state. For details, see "Installation Location" on page 3-1.
■ Relay output type
There are no usage restrictions for input and output I/O.
■ Transistor sink output type
There are no usage restrictions for input and output I/O when no cartridges are installed.
When a cartridge is installed, reduce the input voltage and I/O simultaneous ON ratio (a%) as shown in the following diagrams.
24V DC Power Type
Input I/O
Input Voltage (V DC)
28.8 V
24.0 V
0 V
0%
12V DC Power Type
Input I/O
Input Voltage (V DC)
18.0 V
12.0 V
0 V
0%
* The values in parentheses are for the CAN J1939 All-in-One CPU module.
Ambient
Input Voltage (V DC)
Temperature
45°C
Ambient
Temperature
55°C
I/O Simultaneous
ON Ratio (%)
70%
80%
100%
Ambient
Input Voltage (V DC)
Temperature
45°C
(16.0 V
Ambient
Temperature
55°C
I/O Simultaneous
70%
80%
100%
ON Ratio (%)
FC6A S
MICROS
ERIES
MART
Output I/O
28.8 V
24.0 V
0 V
0%
Output I/O
18.0 V
**
)
12.0 V
0 V
0%
U
'
M
FC9Y-B1722
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
Ambient
Temperature
45°C
Ambient
Temperature
55°C
I/O Simultaneous
ON Ratio (%)
70%
80%
100%
Ambient
Temperature
45°C
Ambient
Temperature
55°C
I/O Simultaneous
70%
80%
100%
ON Ratio (%)