■ All-in-One CPU Module Only
Analog Potentiometer
Points
Data Resolution
Analog Input
Points
Input Range
Data Resolution
Input Impedance
Error
Input Delay Time
Maximum Allowed Steady Load
Isolation
Cable
Serial Port 1
Points
Communication Type
Maximum Communication Speed
Communication Functions
Connector
Cable
Maximum Cable Length
Isolation between Internal Circuit
■ CAN J1939 All-in-One CPU Module Only
CAN Port
Points
Communication Type
Communication Speed
Communication Functions
Connector
Cable
Maximum Cable Length
Terminating Resistance
Isolation between Internal Circuit
1
0 to 1,000
1
0 to 10 V
0 to 1,000
Approx. 100 kΩ
±1% of full scale (±5% of full scale when noise is applied)
12 ms (including the software filter)
13 V
Not isolated
Unshielded cable 1 m (included with the product)
1 (ports can be added that are capable of using RS-232C or RS-485 communication by using
cartridges.)
EIA RS-232C or RS-485 software selectable
115,200 bps
Maintenance communication, user communication, Modbus communication, data link
communication
RJ45
RS232C: Shielded multicore
RS485: Shielded twisted-pair
RS-232C: 5 m
RS-485 : 200 m
Not isolated
1
CAN bus communication
250 kbps
J1939 communication
FC6A-PMTE05PN02
SAE-J1939-11
: Shielded twisted-pair
SAE-J1939-15
: Unshielded twisted-pair
SAE-J1939-11
: 40 m, stub 1 m maximum
SAE-J1939-15
: 40 m, stub 3 m maximum
120 Ω (0.5 W or higher)
Power supply:
Transformer isolated
Signal:
Galvanic isolation, photocoupler isolated