Troubleshooting Diagram 2
The Run LED [RUN] is not On
The run LED [RUN] turns on when the PLC is running.
The run LED [RUN] is not on.
Is the error LED [ERR] on?
Click the Start button in WindLDR on a
computer connected to the FC6A Series
MICROSmart.
Is the run LED [RUN] on?
Monitor M8000 (start control special
internal relay) using WindLDR.
YES
Turn on M8000 using WindLDR.
Is the run LED [RUN] on?
13-10
YES
NO
YES
NO
Is M8000 on?
NO
YES
NO
FC6A S
MICROS
ERIES
See Troubleshooting Diagram 3,
"The Error LED [ERR] is On"
Note: The Start button is found in the WindLDR menu bar.
Note: To monitor M8000, from the WindLDR menu bar, select Online >
Monitor > Monitor, then Online > Custom > New Custom Monitor. Enter
M8000 in the Device box in the Custom Monitor dialog box.
Note: To turn on M8000, enter 1 in the Current Value box in the
Custom Monitor dialog box.
NO
switch or the function switch
used to run/stop the PLC?
Turn off the stop/reset input and set the
Call IDEC for assistance.
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
Is the stop/reset input
YES
function switch to "1."
Is the run LED [RUN] on?
NO
YES
END