Editing Programs

This section describes how to reflect TP (timer preset values) and CP (counter preset values) in the user program and how to clear them.
Reflecting TP (Timer Preset Values) and CP (Counter Preset Values) in the User Program
Note: Even if you modify TP (timer preset values) and CP (counter preset values) using the function in "Monitoring Device Values" on page 7-32,
those changes are not reflected in the user program at that time. To reflect the changed preset values in the user program, you must stop the user
program and confirm the changes.
When you change TP (timer preset values) and CP (counter preset values) with the function in "Monitoring Device Values" on page
7-32 and attempt to leave device monitor mode, the following message is displayed.
Timer/counter preset
values are changed.
Press the
(ESC) button or the
1.
When the user program is running
Running
T/C is changed
2015/DEC/01/TUE
13:30:40
When TP (timer preset values) and CP (counter preset values) differ from the device values in the ROM, T/C is changed is
displayed on the standard screen.
To reflect or clear preset value changes, stop the user program. For the steps to stop the user program, see "Switching run/stop"
on page 7-9.
Stopped
T/C is changed
2015/DEC/01/TUE
13:30:40
2.
On the standard screen, press the
Run
Edit Program
External Memory
Configurations
3.
Select Edit Program with the
Run
Edit Program
External Memory
Configurations
Select T/C Preset Values and press the
4.
T/C Preset Values
Select Confirm with the
5.
T/C Change Status:
T/C is changed
Clear
Confirm
The changed preset values are written to the user program in the ROM.
7-10
(OK) button to display the standard screen.
When the user program is stopped
Stopped
T/C is changed
2015/DEC/01/TUE
13:30:40
(ESC) +
(OK) buttons to display the system menu.
(up) and
(down) buttons and press the
(OK) button.
(up) and
(down) buttons and press the
FC6A S
MICROS
ERIES
MART
(OK) button.
(OK) button.
U
'
M
FC9Y-B1722
SER
S
ANUAL

Advertisement

Table of Contents
loading

Table of Contents