Function Switch Configuration

This section describes the function of the function switch on the front of the FC6A Series MICROSmart.
Function Description
When Function switch is 0, special internal relay M8073 (Function switch status) turns off. When Function switch is 1, M8073 turns
on. The function switch can be used as an external switch by using M8073.
When special internal relay M8000 (start control) is on, running and stopping the FC6A Series MICROSmart can be controlled with
the function switch.
Notes:
Stop input and reset input have priority over the status of M8000.
Enabled is the default setting for Run/Stop PLC by Function Switch and Turn on M8000 when function switch is changed from
"0" to "1". in WindLDR.
When RUN/STOP PLC by Function Switch is disabled
RUN/STOP status
(When RUN/STOP control setting disabled)
Function switch status
(1) The FC6A Series MICROSmart run/stop status is controlled by the status of M8000, regardless of the function switch.
*
M8073 turns on and off according to the status of the function switch.
When RUN/STOP PLC by Function Switch is enabled and Turn on M8000 when function switch is changed from "0" to
"1". is disabled
RUN/STOP status
(When RUN/STOP control setting disabled)
Function switch status
(1) When the function switch is 0, the FC6A Series MICROSmart remains in the stopped state, even when M8000 is turned on.
(2) When the function switch is changed from 0 to 1, the FC6A Series MICROSmart runs or stops according to the status of
M8000.
(3) When the function switch is 1, the FC6A Series MICROSmart stops when M8000 is turned off.
(4) When the function switch is changed from 1 to 0, the FC6A Series MICROSmart stops.
*
M8073 turns on and off according to the status of the function switch.
(1)
RUN
STOP
ON
Start control
(M8000)
OFF
Function switch
1
0
ON
(M8073)
OFF
(1)
RUN
STOP
Start control
ON
(M8000)
OFF
Function switch
1
0
ON
(M8073)
OFF
FC6A S
MICROS
ERIES
(1)
(2)
(3)
(2)
(3)
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
5: F
S
UNCTIONS AND
(2)
(4)
ETTINGS