2: P
S
RODUCT
PECIFICATIONS
Isolation
Cable
Run/Stop Methods
Power on/off
WindLDR RUN/STOP command
Function switch operation
USB Port
Points
Communication Type
Communication Functions
Connector
Isolation between Internal Circuit
Available Function when FC6A is
Powered by USB
Ethernet Port
Points
Communication Type
Communication Speed
Port 1
Communication
Functions
Port 2
Connector
Cable
Maximum Cable Length
Isolation between Internal Circuit
SD Memory Card Slot
Points
Supported SD Card
File System
Function
Insertion/Removal Durability
Communication Connector
Cartridge Base Module
Connection
HMI Module Connection
2-44
Not isolated
Unshielded cable 1 m (included with the product)
1
USB2.0 Full speed, CDC class
Capable of maintenance communication with a PC
USB mini-B
Not isolated
Downloading/uploading user programs, downloading system software, data file manager
2
(When the HMI module is connected, this can be expanded by 1 point with the Ethernet
port that has the web server function.)
IEEE 802.3 compliant
10BASE-T, 100BASE-TX
Maintenance communication server,
User communication server/client (TCP/UDP),
Modbus TCP server/client,
PING, SNTP, e-mail, web server, FTP server/client, BACnet/IP
Maintenance communication server,
User communication server/client (TCP/UDP),
Modbus TCP server/client,
PING
RJ45 (Auto MDI/MDI-X compatible)
CAT 5 or higher, STP
100 m
Pulse transformer isolated
1
SD memory cards (max 2 GB), SDHC memory cards (max 32 GB)
FAT16, FAT32
Downloading/uploading user programs, saving log data,
recipes, downloading system software, saving web pages
2,000 times
1
No. of
(Two cartridges can be connected to the cartridge base module when it is connected to the
Modules
Plus CPU module.)
1
No. of
(One cartridge can be connected to the HMI module when it is connected to the Plus CPU
Modules
module.)