Relay Output Specifications
■ 24V DC Power Type
Type No.
No. of Outputs
Output Points per
Common Line
Terminal Arrangement
Output Type
*1
Maximum Load Current
Minimum Switching Load
Initial Contact Resistance
Electrical Life
Mechanical Life
*1
Rated Load
Withstand Voltage
I/O Terminal Connector
*1 Values for resistive/inductive load.
Output Delay
ON
Input to Relay
OFF
ON
Output Relay Status
OFF
8
COM1
4
COM2
4
See "24V DC Power Type" on page 2-51.
1a contact
1
2 A maximum
1 Common
7 A maximum
1.0 mA/5.0V DC (reference value)
30 mΩ or lower
100,000 operations minimum (rated load 1,800 operations/hour)
20,000,000 operations minimum (no load 18,000 operations/hour)
240V AC 2 A, 30V DC 2 A
Between Output
2,300V AC, 1 minute
Terminal and FE
Between Output
Terminal and
2,300V AC, 1 minute
Internal Circuit
Between Output
2,300V AC, 1 minute
Terminals (COMs)
Type
See "24V DC Power Type" on page 2-51.
Insertion/Removal
100 times minimum
Durability
FC6A S
MICROS
ERIES
FC6A-D16R1CEE
OFF Bounce:
6 ms maximum
OFF Delay:
10 ms maximum
ON Bounce:
6 ms maximum
ON Delay:
6 ms maximum
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
2-47

Advertisement

Table of Contents
loading

Table of Contents