IDEC MICROSmart FC6A Series User Manual page 439

Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

(2) Data Type
The analog input value can be handled as the set data type. There are seven data types for the analog inputs.
Yes: Supported,
: Not supported
Data Type
FC6A-J2C1
*1
Binary data
Yes
*1
Optional range
Yes
*2
Celsius
*2
Fahrenheit
*3
Resistance
Binary data
(16 bits)
Optional range
(16 bits)
*1 For only the FC6A-J8A1, binary data (12 bits) and optional range (12 bits) are displayed.
*2 Can only be set when the signal type is thermocouple, resistance thermometer or NTC thermistor.
*3 Resistance when using the FC6A-J8CU1 and the signal type is set to PTC thermistor or Resistance measurement.
*4 Binary data (16 bits) and optional range (16 bits) can be used with the following versions.
FC6A-J8A1: Version 200 or later
WindLDR: Version 8.6.0 or later
If a FC6A-J8A1 that does not correspond to the above version numbers is set to binary data (16 bits) or optional range (16 bits), an error will
occur and the module will operate as binary data (12 bits).
(3) Minimum and maximum values
The analog input values are stored in data registers. The stored minimum and maximum values are determined by the set signal
type and data type. A parameter setting error occurs when a value is set that exceeds the minimum or maximum value.
The minimum and maximum values that correspond to the signal type and data types are as follows.
Signal Type
0 to 10 V
0 to 65,535
-10 to +10 V
-32,768 to 32,767 -32,768 to 32,767
0 to 20 mA
0 to 65,535
4 to 20 mA
0 to 65,535
Type K thermocouple
0 to 65,535
Type J thermocouple
0 to 65,535
Type R thermocouple
0 to 65,535
Type S thermocouple
0 to 65,535
Type B thermocouple
0 to 65,535
Type E thermocouple
0 to 65,535
Type T thermocouple
0 to 65,535
Type N thermocouple
0 to 65,535
Type C thermocouple
0 to 65,535
Pt100
0 to 65,535
Pt1000
0 to 65,535
NI100
0 to 65,535
NI1000
0 to 65,535
NTC thermistor
0 to 65,535
PTC thermistor
0 to 65,535
PTC thermistor (threshold)
1/2/4
Resistance measurement
0 to 65,535
Expansion 0 to 20 mA
0 to 4,095
Expansion 4 to 20 mA
0 to 4,095
*1 For only the FC6A-J8A1, binary data (12 bits) and optional range (12 bits).
*2 The minimum and maximum values can be set only when the data type is set to optional range. Set the minimum and maximum values
between -32,768 and 32,767.
FC6A-J4A1
FC6A-J8A1
Yes
Yes
Yes
Yes
Yes
Yes
Optional
Binary Data
Range
*1
(12 Bits)
*1*2
(12 Bits)
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767 -2,000 to 13,000 -3,280 to 23,720
-32,768 to 32,767 -2,000 to 10,000 -3,280 to 18,320
-32,768 to 32,767 0 to 17,600
-32,768 to 32,767 0 to 17,600
-32,768 to 32,767 0 to 18,200
-32,768 to 32,767 -2,000 to 8,000
-32,768 to 32,767 -2,000 to 4,000
-32,768 to 32,767 -2,000 to 13,000 -3,280 to 23,720
-32,768 to 32,767 0 to 23,150
-32,768 to 32,767 -2,000 to 8,500
-32,768 to 32,767 -2,000 to 6,000
-32,768 to 32,767 -600 to 1,800
-32,768 to 32,767 -600 to 1,800
-32,768 to 32,767 -900 to 1,500
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
FC6A S
MICROS
ERIES
FC6A-J4CN1 FC6A-J4CH1Y FC6A-J8CU1 FC6A-L06A1 FC6A-L03CN1
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
*4
*4
Data Type
Celsius
Fahrenheit
320 to 32,000
320 to 32,000
320 to 33,080
-3,280 to 14,720
-3,280 to 7,520
320 to 41,990
-3,280 to 15,620
-3,280 to 11,120
-760 to 3,560
-760 to 3,560
-1,300 to 3,020
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
9: A
NALOG
Yes
Yes
Yes
Yes
Yes
Binary Data
Resistance
(16 Bits)
0 to 65,535
-32,768 to 32,767 -32,768 to 32,767
0 to 65,535
0 to 65,535
100 to 10,000
100 to 32,000
0 to 65,535
0 to 65,535
I/O M
ODULES
Yes
Yes
Yes
Yes
Yes
Yes
Optional
Range
(16 Bits)
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
-32,768 to 32,767
9-5