Advertisement

10: I/O C
ARTRIDGES
Digital I/O Cartridge Parameters
Input filter settings are the only parameters available.
Parameters can be configured for only digital input cartridges.
Input filter settings can be configured for each digital input.
Input Filter
The input filter is used to adjust the filter width according to the width of the input signal in order to decrease the effects of input
contact bounce and noise.
The filter width can be adjusted to a value of 0 ms (no input filter) and 3 to 15 ms (1-ms increments) for each digital input.
For details on the input filter, see "Input Filter" on page 5-42.
Setting Details
Filter Time (ms)
0
3 to 15
Setting Procedure
To use digital I/O cartridges, you must configure the digital I/O cartridges that will be used with the Module Configuration Editor in
WindLDR and download the user program to the FC6A.
For basic Module Configuration Editor operations, see "Module Configuration Editor" on page 12-1.
This section describes how to insert digital I/O cartridges into the module configuration area and how to configure the input filter.
Select the digital I/O cartridge in the expansion modules and cartridges list and drag and drop it to the module configuration area.
1.
10-4
Set the digital input filter time in 1-ms increments.