IDEC MICROSmart FC6A Series User Manual page 126

Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

2: P
S
RODUCT
PECIFICATIONS
(3) Control Output LEDs [OUT0, OUT1]
On: Control output is on
Off: Control output is off
Flashing: For current output only, flashes at the duty cycle that corresponds to the output manipulated variable in a 100 ms
cycle.
For an output manipulated variable of 20%, the LED is on for 20 ms and off for 80 ms.
(4) Event Output LEDs [EVT0, EVT1]
On: When alarm 1 to alarm 8 or a loop error alarm has occurred
Off: When no alarms have occurred
(5) Auto Tuning/auto Reset LEDs [AT0, AT1]
Flashing: When executing auto tuning or auto reset
Off: When auto tuning or auto reset is stopped
(6) Manual Mode LEDs [MT0, MT1]
On: When program control mode is selected
Off: When auto mode is selected
(7) Fixed Value Control Mode/program Control Mode LEDs [F/P0, F/P1]
On: During program control mode
Off: During fixed value control mode
(8) Program Control Execution/hold LEDs [R/H0, R/H1]
On: During program control execution or while control is allowed in fixed value control
Flashing: When there is a power interruption during program control hold or during program control execution
Off: During program control stopped or while control prohibited in fixed value control
(9) External SP Enabled/disabled LEDs [R/L]
On: External SP input is enabled
Off: External SP input is disabled
(10) Terminal Name Label
Indicates terminal numbers.
(11) Cable terminals
These terminals are for connecting cables. Terminal block type (3.81 mm pitch), spring clamp system.
(12) Expansion connector
Connects the expansion modules and the CPU module.
Model List
Module type
Non-contact voltage output
(to drive SSRs)/current
output type
Relay contact output type
2-96
Cable Terminal Type
I/O Points
Input
Terminal block type
(3.81 mm pitch)
Output
Input
Terminal block type
(3.81 mm pitch)
Output
FC6A S
MICROS
ERIES
Voltage input (0 to 10 V, 0 to 5 V, 1 to 5 V, 0 to 1 V)
Current input (4 to 20 mA, 0 to 20 mA)
2
Thermocouple (K, J, R, S, B, E, T, N, PL-II, C)
Resistance thermometer (Pt100, jPt100)
Voltage output (12V DC digital output)
2
Current output (4 to 20 mA)
Voltage input (0 to 10 V, 0 to 5 V, 1 to 5 V, 0 to 1 V)
Current input (4 to 20 mA, 0 to 20 mA)
2
Thermocouple (K, J, R, S, B, E, T, N, PL-II, C)
Resistance thermometer (Pt100, jPt100)
2
Relay output
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
I/O Signal
Type No.
FC6A-F2M1
FC6A-F2MR1

Advertisement

Table of Contents
loading

Table of Contents