Self-diagnostic Functions
Keep data
User program (ROM) CRC check
Timer/counter preset value change check
User program syntax check
User program execution check
Watchdog timer check
User program download check
Input Filter
0 ms (no filter), 3 to 15 ms selectable (in 1 ms increments)
Catch Input/Interrupt Input
High-speed 4 Points (I0, I1, I6, I7)
Medium-speed 2 Points (I3, I4)
High-speed Counter
Maximum Counter
Frequency and Points
Count Range
Operation Mode
Pulse Output (Transistor Output Type Only)
Part No.
Points
Maximum output
pulse frequency
Reversible control
PWM output
Function Switch
Points
Function
Run/Stop Methods
Power on/off
WindLDR RUN/STOP command
Function switch operation
Minimum turn on pulse width:
Minimum turn off pulse width:
Minimum turn on pulse width:
Minimum turn off pulse width:
Single-phase, two-phase common:
Single-phase dedicated:
Single-phase, two-phase common:
Single-phase dedicated:
Rotary encoder mode, adding counter mode, frequency measurement mode
FC6A-C16K1CE
FC6A-C24K1CE
FC6A-C16P1CE
FC6A-C24P1CE
4
Q0,Q1: 100kHz
Q2,Q3: 5kHz
Single-pulse output mode: 2axis (Q0-Q3)
Dual-pulse output mode: 1axis (Q0-Q1)
Duty cycle: 0.1 to 100.0 (increments of 0.1%)
Output pulse frequency: 15 to 5,000 (increments of 1Hz)
: 4 points(Q0-Q3)
*Q0,Q1:Adjust min. 5μs as ON time, and min. 15μs as OFF time.
*Q2,Q3:Adjust min. 100μs as ON/OFF time .
1 (2 position slide switch)
Program run/stop
The function can be set in the function area settings (default setting: enabled).
FC6A S
MICROS
ERIES
Power failure
Clock error
Data link connection check
Expansion bus initialization check
System check
SD memory card transfer check
SD memory card access check
5 μs
5 μs
35 μs
35 μs
100 kHz (single-phase 4 points max, two-phase 2 points max)
5 kHz (2 points)
0 to 4,294,967,295 (32 bits)
0 to 4,294,967,295 (32 bits)
FC6A-C40K1CE
FC6A-C40P1CE
FC6A-C40K1DE
FC6A-C40P1DE
Special internal relay (M8000) operation
Operation of stop input and reset input
U
'
M
FC9Y-B1722
MART
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
FC6A-C40K1CEJ
FC6A-C40P1CEJ
FC6A-C40K1DEJ
FC6A-C40P1DEJ
Q0,Q2,Q4,Q6: 100kHz
Single-pulse output mode: 4axis (Q0-Q7)
Dual-pulse output mode: 4axis (Q0-Q7)
Duty cycle: 0.1 to 100.0 (increments of 0.1%)
Output pulse frequency: 15 to 5,000
(increments of 1Hz)
: 4 points(Q0,Q2,Q4,Q6)
*Adjust min. 5μs as ON time, and min. 15μs
as OFF time.
2-13