IDEC MICROSmart FC6A Series User Manual page 113

Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

Function Specifications
■ Analog Input Specifications
Analog Input Module
Type No.
Voltage
Current
Thermocouple
Input Type
and Input
Range
Resistance Thermometer
Thermistor
Resistor
Voltage
Current
Thermocouple
Input
Impedance
Resistance Thermometer
Thermistor
Resistor
Sampling Time
Sampling Repetition Time Sampling time × Number of enabled input channels
Total Input Delay Time
AD
Conversion
Type of Input
Operation Mode
Conversion Method
Maximum Error at 25°C
Input Error
Temperature Coefficient
FC6A-J2C1
FC6A-J4A1
0 to 10 V
-10 to 10 V
4 to 20 mA
0 to 20 mA
1 MΩ or higher
50 Ω or lower
1 MΩ or higher
1 MΩ or higher
1 MΩ or higher
1 MΩ or higher
1 ms
1 ms or 10 ms
*1
Sampling time + Sampling repetition time + 1 scan time
Single-ended
Self-scan
Σ∆ type ADC
±0.1% of full
±0.2% of full scale
scale
0.006%/°C
0.01%/°C
FC6A S
MICROS
ERIES
MART
FC6A-J8A1
FC6A-J4CN1
(K) -200 to 1,300°C (-328 to 2,372°F)
(J) -200 to 1,000°C (-328 to 1,832°F)
(R) 0 to 1,760°C (32 to 3,200°F)
(S) 0 to 1,760°C (32 to 3,200°F)
(B) 0 to 1,820°C (32 to 3,308°F)
(E) -200 to 800°C (-328 to 1,472°F)
(T) -200 to 400°C (-328 to 752°F)
(N) -200 to 1,300°C (-328 to 2,372°F)
(C) 0 to 2,315°C (32 to 4,199°F)
Pt100:
-200 to 850°C
(-328 to
1,562°F)
Pt1000:
-200 to +600°C
(-328 to
1,112°F)
NI100:
-60 to +180°C
(-76 to 356°F)
NI1000:
-60 to +180°C
(-76 to 356°F)
10 ms, 100 ms
or 104 ms
±0.2% of full scale
Cold junction compensation accuracy: ±4.0°C or
lower
Exceptions
R, S: ±6°C (0 to 200°C)
B: Not possible to guarantee accuracy (0 to 300°C)
K, J, E, T, N:
±0.4% of full scale (0°C or lower)
U
'
M
FC9Y-B1722
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
FC6A-J4CH1Y
FC6A-J8CU1
NTC
(-90 to 150°C)
PTC
(100 to 10,000 Ω)
100 to 32,000 Ω
120 ms or 30
104 ms
ms
Differential
Single-ended
input
2-83

Advertisement

Table of Contents
loading

Table of Contents