Dc Output Alarm Thresholds Configuration Example; Displaying Poe Supervision Information - H3C S9500 Series Operation Manual

Routing switches
Hide thumbs Also See for S9500 Series:
Table of Contents

Advertisement

Operation Manual – PoE
H3C S9500 Series Routing Switches
3
4
5
Note:
For both 220 VAC and 110 VAC input, it is recommended to set the upper threshold to
57.0 V and the lower threshold to 45.0 V.

2.3.2 DC Output Alarm Thresholds Configuration Example

I. Network requirements
Set the overvoltage alarm threshold of DC output for the PoE PSUs to 57.0 V.
Set the undervoltage alarm threshold of DC output for the PoE PSUs to 45.0 V.
II. Configuration procedure
# Enter system view.
<H3C> system-view
# Set the overvoltage alarm threshold of DC output for the PoE PSUs to 57.0 V.
[H3C] poe-power output-thresh upper 57.0
# Set the undervoltage alarm threshold of DC output for the PoE PSUs to 45.0 V.
[H3C] poe-power output-thresh lower 45.0
# Display the DC output state of the PoE PSUs.
[H3C] display poe-power dc-output state
# Display the DC output voltage/current values of the PoE PSUs.
[H3C] display poe-power dc-output value

2.4 Displaying PoE Supervision Information

After completing the above configurations, you can execute the display command in
any view to query the PoE state of the switch. Then you can view the display output to
check the effect of these configurations.
Set the undervoltage alarm
threshold of DC output (lower
threshold) for the PoE PSUs
Display the DC output state
of the PoE PSUs.
Display
the
DC
voltage/current value of the
PoE PSUs
Chapter 2 PoE PSU Supervision Configuration
poe-power
output-thresh lower
string
display
poe-power
dc-output state
output
display
poe-power
dc-output value
2-3
Required, and the
range is 45.0 V to
47.0 V.
Optional, and you
can execute this
command in any
view.
Optional, and you
can execute this
command in any
view.