1. Attach the electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
the ESD point on the chassis. There is an ESD point located next to the protective earthing terminal
and below PSU 5 on the MX10000 rear panel (see
MX10016 (see
Figure 101 on page
Figure 100: ESD Point on the MX10008 Chassis Rear
1
1
ESD point
Figure 101: ESD Point on the MX10016 Chassis Rear
1
1
ESD point
2. Flip the power | switch next to the appliance inlet on the power supply to the standby position.
3. If the AC or DC power source outlets have a power switch, set them to the OFF position.
4. Disconnect the Anderson connectors from each input on the JNP10K-PWR-AC2 power supply faceplate.
Figure 100 on page
206).
206) and below PSU_9 on the
206